Building Permit Details
Permit Number: 23-09448
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Residential
Scope of Work: Alteration
Issued Date: 09/07/2023
CO Issue Date:
Plans Examiner: Anthony Petty
Job Address: 1497 FLINTWOOD RD FRANKTOWN, CO 80116
Building Code: 2021 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Final Building 10/30/2023 Disapproved Rick Chadwick 1. Minimum grippable handrail height 34” 2. Caulk all water closet to floor 3. Complete shower inclosure 4. Tempered glazing at window required within 5’ of waters edge at tubs and showers 5. Maximum hot water temperature at tubs and showers 120* 6. Painting at lower rooms vould not check egress  
Final Building 12/18/2023 Approved Rick Chadwick Existing basement bedrooms do not meet egress at windows OK TO PROCEED  
Final Electric 10/30/2023 Disapproved Thomas Buzo Not ready. Courtesy walk only.

This permit is under new 2023NEC requirements. See 210.8 for GFCI protection requirements of Appliances and receptacles.

1)Areas that have been remodel - TR receptacles are required.
2)Spark rings req at kitchen back splash or install boxes flush to finish materials.
3)Receptacles under sink req GFCI and AFCI Protection.
4)Protect DW cord where it passes through cabinet.
5)Install Faceplate throughout project for scope of work.
6)Breaker lock req for hardwire appliances. 422
7)GFCI protection req for 120V -240V receptacles and Appliances as req per 210.8
8)AFCI protection req for all new and modified circuits. 210.12
9)Install all Smoke and CO Detectors as req per 314&315 IRC
 
Final Electric 12/18/2023 Disapproved Justin Lett 1. DW cord requires bushing 2. Both receps above micro require GFCI/AFCI protection 3. AFCI protection for disposal and device required to be TR type 4. Lower dryer requires GFCI protection 5. Plates missing lower laundry 6. Complete smokes/COs lower level-all must interconnect throughout house and will test at next inspection 7. Upper coffee bar AFCI protection required at breaker-new circuit 8. AFCI protection required craft room lights/receps, kitchen counter right of sink, kitchen lighting  
Final Electric 12/20/2023 Disapproved Justin Lett Corrections incomplete—2. Lighting recep above micro require GFCI protection 5. Plate missing lower laundry dryer  
Final Electric 12/21/2023 Approved Justin Lett  
Interior Gas Line 09/08/2023 Disapproved Rick Chadwick Complete gas line  
Interior Gas Line 09/12/2023 Approved Rick Chadwick  
Rough Electric 09/08/2023 Disapproved Justin Lett 2023 NEC-1. Countertop spacing incorrect both sides of sink and at north end of kitchen counter 2. Provide installation instructions for double oven-typically requires 40A minimum branch circuit 3. Correct wall space at dining room wall 4. Nook counter recep required on 20A ckt and 2-4’ spacing 5. Walls at both sides of master bed door are greater than 24” and require receptacles 6. Exhaust fans not wired 7. Smoke alarms required in each bedroom, adjacent to each bedroom, every level. All require commercial power, battery back up, fully interconnected. Battery only alarms not permitted.

Notes for final-check new bathroom HR, lower laundry AFCI/GFCI breakers.

Basement mech sub lacks clearances-existing, non conforming condition

Note-island receps can no longer be located below island counter top and provisions are required to add them.
 
Rough Electric 09/12/2023 Disapproved Justin Lett 2023 NEC- 4. Nook counter recep required on 20A ckt and 2-4’ spacing 6. Exhaust fans not wired 7. Smoke alarms required in each bedroom, adjacent to each bedroom, every level. All require commercial power, battery back up, fully interconnected. Battery only alarms not permitted.  
Rough Electric 09/14/2023 Disapproved Justin Lett Corrections still outstanding-6. Exhaust fans not wired 7. Smoke alarms required in each bedroom, adjacent to each bedroom, every level. All require commercial power, battery back up, fully interconnected. Battery only alarms not permitted.

**Ok to continue insulating/drywall pending frame approval**
 
Rough Electric 10/11/2023 Disapproved Justin Lett Corrections from previous incomplete  
Rough Electric 10/24/2023 Disapproved Justin Lett 1. Smoke alarms required to be placed minimum of 36” horizontally from bathroom doors that contain tub/shower-R314 2. Exhaust fans require NM connectors at cable entry  
Rough Electric 10/30/2023 Approved Thomas Buzo Corrections Made  
Rough Frame 09/08/2023 Disapproved Rick Chadwick 1. Provide min 1/4” plf fall at kitchen trap arm 2. Solid blocking between header members and face nail 3. Complete rough plumbing  
Rough Frame 09/12/2023 Disapproved Rick Chadwick 1. Provide 1;4” plf fall at tub and shower 2. Provide engineering fix for DWV bore mid span within 2” of bottom of joist 3. Overspan at DWV at basement exterior wall 4. Stud shoe at upper level shower vent overbore 5. Foam DWV penetrations at exterior wall upper bathroom 6. Complete add on to permit for remodel of upper mid bathroom 6. Block and face nail header to garage  
Rough Frame 09/14/2023 Disapproved Fredrick Mooney Partial: previous items complete with the exception of:

2. Once added bathroom is updated to permit recall for visual inspection on modified plumbing.
3. Need to verify air gap at large shower overhead shower head supply to unconditioned space. 5 side encapsulation required.
4. Need to verify face nail of header at garage door header.
 
Rough Frame 10/11/2023 Approved Rick Chadwick  
Rough Plumbing 09/19/2023 Disapproved Rick Chadwick 1. S trap at new shower location 2. Foam all penetrations  
Rough Plumbing 09/22/2023 Approved Rick Chadwick  
Shower Pan 09/29/2023 Approved Fredrick Mooney There are 2 Shower Pans to be inspected.