Building Permit Details
Permit Number: 22-04087
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Custom
Scope of Work: New
Issued Date: 09/06/2023
CO Issue Date: 06/10/2024
Plans Examiner: Stuart Foster
Job Address: 5720 DISTANT VIEW PL PARKER, CO 80134
Building Code: 2018 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Caisson/Footer/WG Letter 12/06/2023
Steel Letter 12/06/2023
Survey 12/06/2023
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Construction Meter 09/07/2023 Disapproved Thomas Buzo 1)Need to verify ABB breaker permitted in Utility pedestal. Provide documentation.
2)Connections of conductors to terminals parts shall ensure a thoroughly good connection. - Utility pedestal Grounded and EG conductor lugs. 110.14
3)30” by 36” deep clearance req in front of Utility pedestal. 110.26
4)Raceways contain 4 AWG or larger insulated circuit conductors shall be protected by an identified fitting providing a smoothly rounded insulating surface. 300.4
6)Main disconnect req at Panel. 230.71 (Retention clip will be req of breaker is backfeed 408.36
7)Service disconnect label missing at panelZ
 
Construction Meter 09/12/2023 Disapproved Thomas Buzo 1)Need to verify ABB breaker permitted in Utility pedestal. Provide documentation.  
Construction Meter 09/19/2023 Approved Thomas Buzo CORE 09/19/2023
Driveway Preliminary 04/22/2022 Approved June Amicucci Comply with Douglas County Driveway Standards
Drywall 01/10/2024 Disapproved Rick Chadwick Check all inside corners for proper fastening maximum distance from inside corners to fasteners 4” TERMINATE INSPECTION DID NOT WALK IT ALL  
Drywall 01/12/2024 Approved Rick Chadwick  
Electric Service Equipment 12/26/2023 Cancelled Richard Perrone Not ready, laterals not terminated  
Electric Service Equipment 01/03/2024 Disapproved Thomas Buzo 1)feeders not terminated at pedestal.
2)identify grounded conductors at main disconnects.
3)Remove green bonding screws at house disconnects. 250.24 (float neutrals and grounds)
4)Emergency service disconnect labels missing at disconnects
5)remove paint where ground lugs sit in disconnect enclosures.
6)#6 CU Conductor missing for IBT.
 
Electric Service Equipment 04/26/2024 Approved Curt Elliott CORE 04/29/2024
Electric Service Equipment Partial 01/05/2024 Approved Thomas Buzo Note: GC is waiting on CORE to upgrade existing 200A ped to a 400A. Inspection is needed once new pedestal is set and feeders terminated.  
Electric Trench 12/20/2023 Approved Thomas Buzo Trench from pedestal to house.

(2) 2-4/0Al 1-2/0AL and #2AL EGC

Note: keep ends of trench open at house to verify conduit and bell end fitting.
 
Exterior Lath 04/17/2024 Disapproved Rick Chadwick 1. Weep screed required at bottom throughout  
Exterior Lath 04/22/2024 Approved Fredrick Mooney  
Exterior Wall Sheathing 11/06/2023 Disapproved Fredrick Mooney No plans  
Exterior Wall Sheathing 11/07/2023 Approved Richard Miller  
Final Building 05/22/2024 Disapproved Rick Chadwick 1. Downspout extensions to be 5’ from foundation 2. Splash blocks at si cocks 3. Minimum 6” to grade at stucco 4. Complete sump discharge and paint 5. Provide engineering on retaining walls 6. Grippable handrail at garage stairs 7. Adjust self closing hinges at garage door 8. Flex hose not allowed for trap arm and drum traps are not allowed at laundry sink and bar sink 9. AAV required at master lav 10. Maximum temperature at master tub 120* check all tubs and showers 11. Tempered gl at door to master 12. Minimum standpipe at dishwasher discharge 18” 13. Grippable handrail circumference exceeds 6 inches. 14. Co detector required within 15 feet of basement bedrooms.15. Double wall wye at water heater vent 16. Low transfer combustion air grill to mechanical room  
Final Building 05/30/2024 Approved Rick Chadwick  
Final Electric 05/17/2024 Disapproved Curt Elliott Bedroom 5 closet light may not be over shelf  
Final Electric 05/20/2024 Approved Curt Elliott  
Final Energy Compliance 05/22/2024 Disapproved Rick Chadwick Provide energy report and blower door test and ladder for attic access  
Final Energy Compliance 05/30/2024 Approved Rick Chadwick Install gasket and R-49 insulation to attic access panel CORRECT AND PROCEED  
Insulation Thermal 12/28/2023 Cancelled Bryce Ryberg GC Canceled, not ready  
Insulation Thermal 12/29/2023 Cancelled Rick Chadwick GC called to cancel inspection / not ready  
Insulation Thermal 01/03/2024 Disapproved Dusty Welz 1. Gasket all top plates communicating with attic space.
2. Foam all electrical bone in ceiling communicating with attic.
3. Okay to hang drywall in basement and exterior walls that are already gasketed.
 
Insulation Thermal 01/04/2024 Approved Dusty Welz Corrections verified  
Interior Gas Line 12/20/2023 Approved Fredrick Mooney 10 psi approved. Black Hills Energy 12/21/2023
Midroof 01/23/2024 Approved Rick Chadwick  
Moisture Barrier 04/17/2024 Disapproved Rick Chadwick Provide manufacturer specs on using chicken wire for stone  
Moisture Barrier 04/22/2024 Approved Fredrick Mooney  
Preliminary Defensible Space 04/20/2022 Not Applicable Jill Welle
Roof Truss 11/07/2023 Approved Richard Miller #5665  
Rough Electric 12/19/2023 Disapproved Thomas Buzo **2020NEC**

1)Per DC policy Roof not 100% dried in.
2)Support NM cable every 4.5’ at garage NW corner. 334.30
3)NP - Garage E wall.. check all throughout house (bottom and top plates)
4)UFER wire has not been installed. (This needs to be installed prior to drywall)
5)Correct wall space at master bedroom wall right of hallway. 210.52
6)No more than 4 cables per stack it due bundling check all throughout house. 310.15
7)Staple Nm cable away from edge of framing above 4 gang switch box. (@Kitchen above switch box)
8)Exterior receptacles not permitted on 20A SABC front and rear receptacles. 210.11 and 210.52
10)Receptacle missing at foyer by stair railing. 210.52
11)Receptacle missing at basement unfinished space. 210.52
12)SER feeder cables not installed. This needs to be installed prior to drywall.
13)Connect EGC together at mech room service receptacle. 250.148
14)SD not permitted within 36” of bathroom basement bedroom. IRC314
 
Rough Electric 12/20/2023 Cancelled Thomas Buzo GC Cancelled  
Rough Electric 12/26/2023 Approved Richard Perrone  
Rough Energy Compliance 12/20/2023 Disapproved Fredrick Mooney Draftstopping missed throughout entirety of basement.  
Rough Frame 12/20/2023 Disapproved Fredrick Mooney 1. Dryer vents over maximum length.
2. Draftstopping missed throughout entirety of basement.
3. Strap top plate in basement bedroom north side.
4. Two joist have plumbing pipe in bearing area of joist. North east corner of basement. Need engineer letter.
 
Rough Frame 12/26/2023 Approved Rick Chadwick  
Shower Pan 12/20/2023 Approved Fredrick Mooney  
Ufer Ground Electrode 12/06/2023 Approved Wayne Elmore letter  
Underground Plumbing 10/05/2023 Approved Fredrick Mooney  
Underground Plumbing 10/06/2023 Approved Richard Miller