Building Permit Details
Permit Number:
21-08959
Permit Status:
Completed
Permit Type:
Building
Project Type:
Residential
Description of Work:
RS - Basement
Scope of Work:
Alteration
Issued Date:
08/27/2021
CO Issue Date:
Plans Examiner:
Stuart Foster
Job Address:
5394 SEDONA DR PARKER, CO 80134
Building Code:
2018 IRC
Inspections
Contractors
Permit Fees
Property Details
Structure Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Drywall
11/01/2021
Approved
Rick Chadwick
Print Report
Electric Service Equipment
01/26/2022
Disapproved
Thomas Buzo
Courtesy walk Only. No Inspection.
Note to Homeowner: No record of permit for kitchen remodel. Permit needed for kitchen remodel. New circuits have been added to kitchen that will need to be inspected. Please call with any questions.
Note: Original plans for a 400A service upgrade has been cancelled by the homeowner.(May upgrade in the future) Existing service to remain a 200A. Existing hot tub circuit will be disconnected at hot tub and panel to ensure Service load is below 200A. New branch circuits (Pre wire at this time ) such as new laundry, car charger will remain at locations and will be disconnected at panels and, at outlet boxes will be blanked off. A permit will be require for future 400A service upgrade and for pre wire branch circuits connections.
Print Report
Electric Service Equipment
02/10/2022
Disapproved
Thomas Buzo
Amended
See Final Electric Inspection.
Print Report
Final Building
02/09/2022
Disapproved
Anthony Frank
1) The bedroom is lacking egress compliant ladder attached to the window well.
2) Install the trim cover for the refrigerator box.
3) Install the dishwasher and complete the indirect discharge.
Print Report
Final Building
02/25/2022
Approved
Clayton Rodeback
Print Report
Final Electric
02/10/2022
Disapproved
Thomas Buzo
1) Sub Feeder strands shall not be damage at new basement sub panel terminals. 110.14
2)EGC's shall provide a thoroughly good connection, currently loose on left side of panel. 110.14
3)Terminate all EGC's at New basement sub panel.
4)cap off unused conductors inside sub panels.
5)Secure NM & SER cable within 12" Subpanel Enclosures. (Top and bottom)
6)Install the correct size NM cable connector for New sub panel feeder terminating into existing basement panel.
7)Protect horizontal runs of NM cable in unfinished area of basement.
8)No power to fridge and microwave.
9)GFCI protection req for receptacles within 6' of wet bar sink.
10)GFCI protection req for receptacles under wet bar sink.
11)Open Jboxes in crawl space.
12)Support SER in crawl space and terminate unused ends into boxes, (Can not leave ends hanging in crawl spaces)
13)Light missing in front of water heaters.
14)GFCI receptacles not allowed in ceiling. GFCI receptacles shall be readily accessible.
15)AFCI protection require for receptacles at bottom of stairs. 210.12
16)Hot tub loads puts service over 200A. Per Conversation with EC and GC, Hot tub was gonna be disconnected.
Note: Check exterior service equipment to ensure nothing changed.
Print Report
Final Electric
02/24/2022
Disapproved
Thomas Buzo
7) Protect horizontal runs of NM cable in unfinished area of basement.9)GFCI protection req for receptacles within 6' of wet bar sink. 12) terminate unused ends of service into boxes, (Can not leave ends hanging in crawl spaces)110.14 15)AFCI protection require for receptacles at bottom of stairs. 210.12
Note: Hot tub disconnected at time of inspection.
Service remained unchanged.
Print Report
Final Electric
03/03/2022
Approved
Thomas Buzo
Print Report
Fireblocking
10/21/2021
Approved
Rick Chadwick
Print Report
Interior Gas Line
10/21/2021
Approved
Rick Chadwick
N/A
Print Report
Rough Electric
10/21/2021
Approved
Henry VanSchaack
**service upgrade later **
Print Report
Rough Frame
10/21/2021
Disapproved
Rick Chadwick
1. Minimum stand pipe at auto wash 18” 2. Seal all plate penetrations at sub floor
Print Report
Rough Frame
10/25/2021
Approved
Rick Chadwick
Print Report