Air Conditioner
01/13/2025
Approved
Matt Mazzara
Print Report
Final Electric
01/13/2025
Disapproved
Matt Mazzara
See HVAC
Print Report
Final HVAC
01/13/2025
Disapproved
Matt Mazzara
1)furnace installed is direct vent only per manufacturer, non direct not permitted. Terminations must be performed manufacturer
2)CO dets req within 15’ outside all bedrooms
3)list electric contractor on permit for new electric installed
4)furnace vent terminations not permitted in electric service workspace 110.26
5)ground AC service recep box 250.148 and max #12 conductor at GFCI recep