Building Permit Details
Permit Number:
21-05289
Permit Status:
Voided
Permit Type:
Building
Project Type:
Residential
Description of Work:
RS - Basement
Scope of Work:
Alteration
Issued Date:
06/09/2021
CO Issue Date:
Plans Examiner:
Anthony Petty
Job Address:
9506 CHERRYVALE DR HIGHLANDS RANCH, CO 80126
Building Code:
2018 IRC
Inspections
Contractors
Property Details
Structure Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Drywall
08/02/2021
Approved
Chris Fuller
Basmt
Print Report
Final Building
01/14/2022
Approved
Chris Fuller
Smoke and CEOs tested and interconnected
Print Report
Final Electric
01/14/2022
Disapproved
Damon Montroy
1. AFCI protection required for lights in basement family room.
2. Label new circuits in basement panel.
3. Kitchen island outlet exceeds the maximum of 6” under counter overhang.
4. Wire nuts not allowed for aluminum and copper connections at cook top. Use listed wire connectors.
5. Breaker locks required for double oven and cooktop.
6. GFCI protection required for dishwasher outlet.
7. Bathroom lights on with laundry circuit. GFCI protection required for laundry receptacle.
Print Report
Insulation Thermal
07/27/2021
Approved
Chris Fuller
Fix small area of rim insulation by elec wires
Print Report
Interior Gas Line
07/21/2021
Approved
Chris Fuller
Fireplace holding at 10
Print Report
Rough Electric
07/21/2021
Disapproved
Matt Mazzara
1)4 wire req to double oven
2)micro ded?
3)NP top plate above kitchen 3gang
4)secure LV to maintain 1” clearance to bsmt FP
5)NP by bsmt powder vanity
Note:per Doug Co amendments max 10 openings 15amp circuits, 12 openings 20amp circuits and 4 openings 20amp small appliance circuits that serve kit counter tops
Print Report
Rough Electric
07/27/2021
Approved
Matt Mazzara
Print Report
Rough Frame
07/21/2021
Approved
Chris Fuller
Move toilet flange min 15” from tub
Will check at insulation or drywall insp.
Print Report
Underground Plumbing
06/11/2021
Approved
Chris Fuller
Basmt underground bath group
Print Report