Building Permit Details
Permit Number: 21-00698
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Custom
Scope of Work: New
Issued Date: 04/16/2021
CO Issue Date: 11/30/2021
Plans Examiner: Amanda Hansen, Anthony Petty, Christine Allen, Daniel Davis, Dave Ransom, Donna Martin, Greg Lillmars, Kelly Crowther, Rana Rasteh, Rose Dederick, Stuart Foster, Wayne Elmore
Job Address: 5771 DISTANT VIEW PL PARKER, CO 80134
Building Code: 2018 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Caisson/Footer/WG Letter 08/13/2021
Steel Letter 08/12/2021
Survey 08/12/2021
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Construction Meter 04/19/2021 Disapproved Henry VanSchaack 1) feeder from IREA ped requires an equipment ground; 2) feeder conductors must terminate to lugs, in panel section, jumpers in meter not allowed, plate meter socket; 3) neutral in panel not permitted to be bonded to ground/enclosure; 4) install main breaker in IREA ped, terminate feeder in pedestal  
Construction Meter 04/26/2021 Disapproved Henry VanSchaack 1) neutral smaller than #4 requires white insulation per 200.6; 2) panel neutral not permitted to be bonded to ground/enclosure per 250.24  
Construction Meter 04/27/2021 Approved Justin Lett IREA 04/28/2021
Driveway Form 10/28/2021 Cancelled Jill Welle inspection not required
Driveway Preliminary 01/25/2021 Not Applicable Jill Welle
Drywall 09/22/2021 Disapproved Fredrick Mooney remove drywall screws from durock in the bathrooms and recall. ok to mud and tape.  
Drywall 09/23/2021 Approved Carlo Turchiano  
Electric Service Equipment 09/14/2021 Disapproved Henry VanSchaack 1) pedestal end not terminated
2) identify feeder neutral per 200.6 at both ends
3) identify feeder equipment ground per 250.119 at both ends
4) intersystem bond bar required per 250.94
5) equipment ground terminal not permitted to contact neutral bar in house disconnect
6) no load connected
 
Electric Service Equipment 09/16/2021 Approved Henry VanSchaack IREA 09/17/2021
Electric Trench 09/09/2021 Approved Thomas Buzo Electric trench ok from pedestal to se corner of house. 2-4/0, 1-2/0, 1-1AWG.

Protect direct burial conductor down to 18” below finish grade. Leave trench open at house to check at electric service equipment inspection.
 
Exterior Lath 09/22/2021 Approved Fredrick Mooney complete  
Exterior Underground Gas Line 10/12/2021 Approved Richard Miller #5665  
Exterior Wall Sheathing 07/28/2021 Disapproved Fredrick Mooney Missing hold down straps at garage. Recall.  
Exterior Wall Sheathing 08/06/2021 Approved Richard Miller  
Final Building 11/24/2021 Disapproved Rick Chadwick 1. Maximum gap at riser 4” at garage stairs 2. Caulk all water closet 3. Complete cap at guardrail and handrail 4. Minimum 30” clearance in front of water heater  
Final Building 11/29/2021 Approved Rick Chadwick  
Final Electric 11/23/2021 Disapproved Thomas Buzo 1)IBT needs to be accessible.
2)Extension cords not allowed for GD openers.
3)breaker lock for hood.
4)CO detector in master bedroom when fuel burning appliances are installed within.
5)AFCI CB 16 not holding.

 
Final Electric 11/24/2021 Approved Henry VanSchaack  
Final Energy Compliance 11/24/2021 Disapproved Rick Chadwick Blower door test required  
Final Energy Compliance 11/29/2021 Approved Rick Chadwick  
Foundation Insulation 05/21/2021 Approved Clayton Rodeback Luis moved to 5/21  
Insulation Thermal 09/10/2021 Disapproved Fredrick Mooney 1. Missing vapor barrier on main floor.
2. Missing sill seal.
Ok to rock basement only.
 
Insulation Thermal 09/14/2021 Disapproved Fredrick Mooney requested pictures of missing vapor barrier and sill seal. Never received them.
Do not proceed with drywall on first floor. recall thermal inspection.
 
Insulation Thermal 09/15/2021 Approved Fredrick Mooney Previous items complete.
 
Interior Gas Line 08/11/2021 Cancelled Rick Chadwick No Eng letters.  
Interior Gas Line 08/18/2021 Disapproved Richard Miller 1. Flex connectors not listed for concealed spaces at basement fireplace
2. Gas line needs to be piped into fire box of fireplace
3. Retest system
 
Interior Gas Line 08/28/2021 Cancelled UnassignedBldg Cancelled by Web user.  
Interior Gas Line 09/02/2021 Approved Rick Chadwick Xcel 09/02/2021
Midroof 10/01/2021 Approved Clayton Rodeback  
Preliminary Defensible Space 01/25/2021 Not Applicable Jill Welle
Roof Truss 08/24/2021 Disapproved Carlo Turchiano Check uplift at mid bearing point G5, G3, S6-S13, T18, T19  
Roof Truss 08/25/2021 Disapproved Richard Miller Need bearing blocks on trusses listed in previous inspection at mid point bearing  
Roof Truss 08/27/2021 Approved Clayton Rodeback  
Rough Electric 08/28/2021 Cancelled UnassignedBldg Cancelled by Web user.  
Rough Electric 08/31/2021 Disapproved Justin Lett 1. Dry in garage doors 2. 15A Circuits exceed 10 openings. Comply with DC amendments 3. Correct wall space at bookshelf outside of exercise rm  
Rough Electric 09/02/2021 Approved Jeremy Bock  
Rough Energy Compliance 08/28/2021 Cancelled UnassignedBldg Cancelled by Web user.  
Rough Energy Compliance 09/02/2021 Approved Rick Chadwick  
Rough Frame 08/28/2021 Cancelled UnassignedBldg Cancelled by Web user.  
Rough Frame 09/02/2021 Approved Rick Chadwick  
Rough Plumbing 08/11/2021 Cancelled Rick Chadwick No eng letters.  
Shower Pan 08/18/2021 Approved Richard Miller  
Ufer Ground Electrode 08/13/2021 Approved Wayne Elmore Engineer Letter  
Underground Plumbing 05/21/2021 Cancelled Clayton Rodeback Luis cancelled only the plumbing  
Underground Plumbing 05/24/2021 Cancelled Robert Stratton <><><><><Luis CX<><><>  
Underground Plumbing 05/26/2021 Approved Robert Stratton 5lbs air