Toggle navigation
Building Division Online Services
Department of Public Works Engineering, Building Division
Apply for Permits
Inspections
Schedule Inspections
Cancel Inspections
Searches
Search Contractors
Search Permits
Search Address Jurisdiction
Sign-In
My Profile
Sign Out
Electrical Permit Details
Permit Number:
24-10522
Permit Status:
Completed
Permit Type:
Electrical
Type of Work:
Other
Issued Date:
07/03/2024
Job Address:
7601 PRESERVATION TRL PARKER, CO 80134
Inspections
Contractors
Permit Fees
Property Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Electric Service Equipment
07/12/2024
Cancelled
Curt Elliott
Final inspection needed
Print Report
Electric Trench
07/05/2024
Approved
Justin Lett
Note-1” PVC to front and back water feature
Print Report
Final Electric
07/05/2024
Cancelled
Justin Lett
Cancel-Wrong inspection selected
Print Report
Final Electric
07/05/2024
Disapproved
Justin Lett
1. NM not permitted in exterior raceway 2. Connector required at NM entry into non metallic jbox 3. Sheathing required into jbox 1/4” minimum
Print Report
Final Electric
07/12/2024
Approved
Curt Elliott
Print Report