Building Permit Details
Permit Number: 24-05113
Permit Status: Completed
Permit Type: Building
Project Type: Accessory Use
Description of Work: AU - Garage
Scope of Work: New
Issued Date: 04/23/2024
CO Issue Date:
Plans Examiner: Anthony Petty
Job Address: 2852 MYSTIC DOE CT FRANKTOWN, CO 80116
Building Code: 2021 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Caisson/Footer/WG Letter 04/24/2024
Survey 08/19/2024
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Electric Trench 08/13/2024 Approved Curt Elliott 125’ trench from house to garage. 4/0-4/0-2/0-4 installed in trench.  
Exterior Wall Sheathing 05/30/2024 Approved Rick Chadwick  
Final Building 04/24/2025 Approved Dusty Welz Approved  
Final Electric 08/27/2024 Disapproved Justin Lett 1. Strands cannot be trimmed at breaker in main panel at house or at main lugs in garage panel 2. Opener and high recep in corner both require GFCI protection-GFCI devices required to be readily accessible  
Final Electric 08/29/2024 Approved Curt Elliott  
Moisture Barrier 07/18/2024 Approved Fredrick Mooney  
Monolithic Slab 04/24/2024 Approved Clayton Rodeback  
Roof Truss 05/30/2024 Approved Rick Chadwick  
Rough Electric 08/20/2024 Disapproved Justin Lett 1. Mechanically connect EGCs in all boxes with multiple cables 2. Make up multigang boxes  
Rough Electric 08/21/2024 Approved Justin Lett Inspect garage service at final  
Rough Frame 08/21/2024 Approved Rick Chadwick  
Ufer Ground Electrode 04/25/2024 Approved Justin Lett Stub up at SW corner  
Weather Resistive Barrier 06/06/2024 Approved Rick Chadwick