Building Permit Details
Permit Number: 23-02343
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Residential
Scope of Work: Alteration
Issued Date: 05/02/2023
CO Issue Date:
Plans Examiner: Anthony Petty
Job Address: 10905 S EAST CHERRY CREEK RD ELBERT, CO 80106
Building Code: 2018 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Final Building 06/07/2023 Approved Clayton Rodeback  
Final Electric 06/07/2023 Disapproved Justin Lett 1. TR receps required at island per 406.12 2. GFCI protection required at center recep of island 3. All receps in island require AFCI protection per 210.12 4. Receptacles that serve counter cannot be under overhang greater than 6” 5. Provide crawler access to check jboxes 6. Label all circuits effected by island change at panels 7. Micro recep requires AFCI/GFCI-210.12/210.8. 8. Grommet at DW cord—see notes that were left at rough electric

Note-smokes/CO ok.
 
Final Electric 07/06/2023 Disapproved Justin Lett Correction not completed from previous inspection—3. All receps in island require AFCI protection per 210.12-DW & Disposal circuits still require AFCI protection per 210.12/406.4(D)  
Final Electric 07/12/2023 Disapproved Justin Lett No access—DC employees are not allowed to enter occupied residence without adult present.  
Final Electric 07/14/2023 Approved Justin Lett Note-dual function breakers installed.  
Interior Gas Line 05/05/2023 Approved Rick Chadwick  
Rough Electric 05/04/2023 Approved Justin Lett Island only modification. Exterior walls left as is with new devices only.

1. Need 3 receps to cover island counter square footage requirement 2. Add recep to cover wall space of island per 210.52-can be fed from island recep circuit as long as that circuit does not have more than 4 receps per DC amendment to NEC-will verify at final

Notes for final-TR recep at micro, AFCI/GFCI protection per 210.12/210.8/406.4, DW cord need grommet

Note-smoke alarms required in each bedroom, adjacent to each bedroom, every level. All require commercial power, battery back up, fully interconnected

 
Rough Frame 05/05/2023 Approved Rick Chadwick  
Rough HVAC 06/07/2023 Approved Clayton Rodeback