Building Permit Details
Permit Number: 23-01258
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Residential
Scope of Work: Alteration
Issued Date: 02/23/2023
CO Issue Date:
Plans Examiner: Anthony Petty
Job Address: 8879 TAPPY TOORIE CIR HIGHLANDS RANCH, CO 80129
Building Code: 2018 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Drywall 03/20/2023 Approved Nick Martinell  
Final Building 05/19/2023 Disapproved Robert Stratton No answer at doorbell or knock several times  
Final Building 06/30/2023 Approved Brian Schroder  
Final Electric 05/19/2023 Disapproved Jonathan Pastore 1. Pendant fixture shall not be installed above bathrub
2. Provide UL listing of bathtub
3. Provide UL listing for illuminated mirrors
(Mirror case bonded?)
 
Final Electric 06/30/2023 Approved Richard Perrone  
Interior Gas Line 03/09/2023 Approved Brian Schroder NA  
Rough Electric 03/10/2023 Disapproved Matt Mazzara 1)ENT must secure to box by fitting, floor heat
2)cord for tub not permitted concealed in floor, req raceway
3)bidet recep not permitted within 3’ of tub rim
4)tape/mud jbox garage ceiling, living space above
Note:per Doug Co amendments max 10 openings 15amp circuits and 12 openings 20amp circuits
 
Rough Electric 03/13/2023 Approved Henry VanSchaack ** patch behind j-box on garage ceiling, will check at final **  
Rough Frame 03/09/2023 Approved Brian Schroder  
Shower Pan 03/13/2023 Approved Brian Schroder  
Slab Electrical 03/27/2023 Disapproved Henry VanSchaack Floor heat cable not permitted in closet per 424.38  
Slab Electrical 03/28/2023 Approved Richard Perrone Cables removed from closet