Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Final Building 03/29/2023 Disapproved Henry VanSchaack Provide 3rd party documentation for structural attachment of antennas to tower  
Final Electric 03/29/2023 Disapproved Henry VanSchaack 1) Working clearance required in front of PPC per 110.26
2) bushings required on conduits enclosing #4 and larger conductors in HPL3 cabinet per 300.4
 
Final Electric 07/31/2023 Disapproved Henry VanSchaack Corrections not done
** 30” wide, 36” deep, from ground to 6’-6” above ground in front of transfer panel **