Toggle navigation
Building Division Online Services
Department of Public Works Engineering, Building Division
Apply for Permits
Inspections
Schedule Inspections
Cancel Inspections
Searches
Search Contractors
Search Permits
Search Address Jurisdiction
Sign-In
My Profile
Sign Out
Building Permit Details
Permit Number:
22-06506
Permit Status:
Voided
Permit Type:
Building
Project Type:
Commercial
Description of Work:
CM - Cell Site
Scope of Work:
Alteration
Issued Date:
08/18/2022
CO Issue Date:
Plans Examiner:
Anthony Petty
Job Address:
12185 B DUMONT WAY LITTLETON, CO 80125
Building Code:
2018 IBC
Inspections
Contractors
Property Details
Structure Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Final Building
03/29/2023
Disapproved
Henry VanSchaack
Provide 3rd party documentation for structural attachment of antennas to tower
Print Report
Final Electric
03/29/2023
Disapproved
Henry VanSchaack
1) Working clearance required in front of PPC per 110.26
2) bushings required on conduits enclosing #4 and larger conductors in HPL3 cabinet per 300.4
Print Report
Final Electric
07/31/2023
Disapproved
Henry VanSchaack
Corrections not done
** 30” wide, 36” deep, from ground to 6’-6” above ground in front of transfer panel **
Print Report