Building Permit Details
Permit Number: 22-02559
Permit Status: Completed
Permit Type: Building
Project Type: Commercial
Description of Work: CM - Cell Site
Scope of Work: Alteration
Issued Date: 04/27/2022
CO Issue Date:
Plans Examiner: Anthony Petty
Job Address: 565 A FLINTWOOD RD FRANKTOWN, CO 80116
Building Code: 2018 IBC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Caisson/Footer/WG Letter 06/27/2023
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Electric Service Equipment 06/08/2023 Disapproved Justin Lett 1. Listed add-a-lugs required at neutral bar in fused disconnect 2. Provide accurate fault current value-per CORE, fault current at transformer is 6944 3. Arc flash labels required 4. Completely backfill trench adjacent to transformer 5. Signs required per 702.7(A), (B), (C)-can do these signs at final
 
Electric Service Equipment 06/21/2023 Cancelled Justin Lett Cancelled and created partial to release meter. Not all corrections were completed. See notes on partial inspection result  
Electric Service Equipment 08/03/2023 Approved Justin Lett  
Electric Service Equipment Partial 06/21/2023 Approved Justin Lett Items not corrected from previous. 1. NEW ITEM-Provide barriers at supply side terminations in disconnect-forgot to note this at last inspection 2. Provide accurate fault current value-per CORE, fault current at transformer is 6944 3. Arc flash labels required 5. Signs required per 702.7(A), (B), (C)-can do these signs at final.

Ok for meter release and can check items at next inspection.
CORE 06/22/2023
Electric Trench 11/09/2022 Approved Justin Lett Note-3” PVC service conduit transformer to transfer switch  
Final Building 08/03/2023 Approved Justin Lett See structural analysis in docs  
Final Electric 08/03/2023 Approved Justin Lett Correct fault current value-noted value exceeds what current utility transformer would produce-CORRECT AND PROCEED