Building Permit Details
Permit Number:
22-02559
Permit Status:
Completed
Permit Type:
Building
Project Type:
Commercial
Description of Work:
CM - Cell Site
Scope of Work:
Alteration
Issued Date:
04/27/2022
CO Issue Date:
Plans Examiner:
Anthony Petty
Job Address:
565 A FLINTWOOD RD FRANKTOWN, CO 80116
Building Code:
2018 IBC
Inspections
Contractors
Permit Fees
Property Details
Structure Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Caisson/Footer/WG Letter
06/27/2023
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Electric Service Equipment
06/08/2023
Disapproved
Justin Lett
1. Listed add-a-lugs required at neutral bar in fused disconnect 2. Provide accurate fault current value-per CORE, fault current at transformer is 6944 3. Arc flash labels required 4. Completely backfill trench adjacent to transformer 5. Signs required per 702.7(A), (B), (C)-can do these signs at final
Print Report
Electric Service Equipment
06/21/2023
Cancelled
Justin Lett
Cancelled and created partial to release meter. Not all corrections were completed. See notes on partial inspection result
Print Report
Electric Service Equipment
08/03/2023
Approved
Justin Lett
Print Report
Electric Service Equipment Partial
06/21/2023
Approved
Justin Lett
Items not corrected from previous. 1. NEW ITEM-Provide barriers at supply side terminations in disconnect-forgot to note this at last inspection 2. Provide accurate fault current value-per CORE, fault current at transformer is 6944 3. Arc flash labels required 5. Signs required per 702.7(A), (B), (C)-can do these signs at final.
Ok for meter release and can check items at next inspection.
CORE 06/22/2023
Print Report
Electric Trench
11/09/2022
Approved
Justin Lett
Note-3” PVC service conduit transformer to transfer switch
Print Report
Final Building
08/03/2023
Approved
Justin Lett
See structural analysis in docs
Print Report
Final Electric
08/03/2023
Approved
Justin Lett
Correct fault current value-noted value exceeds what current utility transformer would produce-CORRECT AND PROCEED
Print Report