Toggle navigation
Building Division Online Services
Department of Public Works Engineering, Building Division
Apply for Permits
Inspections
Schedule Inspections
Cancel Inspections
Searches
Search Contractors
Search Permits
Search Address Jurisdiction
Sign-In
My Profile
Sign Out
Electrical Permit Details
Permit Number:
22-01637
Permit Status:
Completed
Permit Type:
Electrical
Type of Work:
Service Change/Upgrade
Issued Date:
02/15/2022
Job Address:
818 POPPYWOOD PL HIGHLANDS RANCH, CO 80126
Inspections
Contractors
Permit Fees
Property Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Electric Service Equipment
02/24/2022
Disapproved
Matt Mazzara
See final electric
Print Report
Electric Service Equipment
04/25/2022
Approved
Matt Mazzara
Xcel 04/26/2022
Print Report
Final Electric
02/24/2022
Disapproved
Matt Mazzara
1)cold water pipe GEC must terminate within first 5’ of entry 250.68(C)
2)#4cu jumper req at water meter 250.102
3)#4cu req to bond service entrance conductor metal raceway 250.102
4)GECs must terminate with neutral at service 250.24
Note:talked with homeowner about electric for new FP req inspected
Print Report
Final Electric
04/25/2022
Approved
Matt Mazzara
Electric for new spa also provided
Print Report