Job Address: 6784 AMHERST CT HIGHLANDS RANCH, CO 80130
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Final Electric 11/03/2021 Disapproved Henry VanSchaack 1) trench inspection was not done, pothole below disconnect, at slab and in between to verify depth
2) hot tub side must be open for inspection of controller inside tub
3) #6 solid copper conductor not permitted in conduit per 310.106
 
Final Electric 12/01/2021 Approved Henry VanSchaack