Electrical Permit Details
Permit Number:
21-02174
Permit Status:
Voided
Permit Type:
Electrical
Type of Work:
Service Change/Upgrade
Issued Date:
03/09/2021
Job Address:
663 WALDEN CT HIGHLANDS RANCH, CO 80126
Inspections
Contractors
Property Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Electric Service Equipment
03/10/2021
Approved
Matt Mazzara
Xcel 03/11/2021
Print Report
Final Electric
03/10/2021
Disapproved
Matt Mazzara
1)handle tie req multiwire branch circuit disposal/dishwasher
2)inter system bond req at service
3)1 conductor per grd rod clamp
4)cold water pipe GEC must terminate within first 5’ of entry
Print Report