Building Permit Details
Permit Number: 19-14278
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Residential
Scope of Work: Addition
Issued Date: 01/30/2020
CO Issue Date:
Plans Examiner: Amanda Hansen, Anthony Petty, Christine Allen, Daniel Davis, Dave Ransom, Donna Martin, Greg Lillmars, Kelly Crowther, Rana Rasteh, Rose Dederick, Stuart Foster, Wayne Elmore
Job Address: 4500 LAMBERT RANCH TRL SEDALIA, CO 80135
Building Code: 2012 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Caisson/Footer/WG Letter 04/09/2020
Steel Letter 04/09/2020
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Drywall 04/29/2020 Approved Kerry Keller  
Drywall 05/15/2020 Approved Kerry Keller  
Exterior Lath 05/28/2020 Approved Kerry Keller  
Exterior Wall Sheathing 03/25/2020 Disapproved Kerry Keller Nail off around all windows and doors
Check all fasteners and sheathing recall
 
Exterior Wall Sheathing 04/14/2020 Approved Kerry Keller  
Final Building 08/26/2020 Approved Clayton Rodeback  
Final Electric 08/26/2020 Disapproved Rick Sugar Gfci required for the refrigerator outlet
Complete lighting in the GYM
 
Final Electric 09/17/2020 Approved Rick Sugar  
Final Energy Compliance 08/26/2020 Approved Clayton Rodeback  
Insulation Thermal 04/21/2020 Approved Kerry Keller  
Interior Gas Line 04/14/2020 Approved Kerry Keller  
Moisture Barrier 05/28/2020 Approved Kerry Keller  
Rough Electric 04/14/2020 Disapproved Rick Sugar Separate no cables NW corner of office
Outlet at S exercise rm wall must be accessible
NP required NE corner of the exercise room
Bond cost per manufacturer specs
Notes
Need to inspect met in exercise ceiling
HRs not terminated
Load calculation for the out building
Size of ocpd feed to panel
 
Rough Electric 04/16/2020 Approved Rick Sugar Need load calculation for the out building
Check home run terminations
2 junction boxes in the basement bedroom ceiling in and out of the closet
 
Rough Energy Compliance 04/14/2020 Approved Kerry Keller  
Rough Frame 04/14/2020 Approved Kerry Keller  
Rough Frame 05/11/2020 Approved Kerry Keller Main house bedroom and bathroom  
Shower Pan 05/20/2020 Approved Clayton Rodeback  
Slab Electrical 06/17/2020 Disapproved Rick Sugar Thermostat and control wire must be in a listed raceway
NM box must be listed for a raceway
Dedicated circuit.?
 
Slab Electrical 06/19/2020 Disapproved Rick Sugar Bond remodel box
Ok to tile floor
 
Underground Plumbing 03/11/2020 Approved Kerry Keller  
Weather Resistive Barrier 04/27/2020 Approved Kerry Keller