Toggle navigation
Building Division Online Services
Department of Public Works Engineering, Building Division
Apply for Permits
Inspections
Schedule Inspections
Cancel Inspections
Searches
Search Contractors
Search Permits
Search Address Jurisdiction
Sign-In
My Profile
Sign Out
Building Permit Details
Permit Number:
19-06860
Permit Status:
Completed
Permit Type:
Building
Project Type:
Commercial
Description of Work:
CM - Tenant Finish
Scope of Work:
Alteration
Issued Date:
07/16/2019
CO Issue Date:
09/05/2019
Plans Examiner:
Kelly Crowther, Wayne Elmore
Job Address:
16830 NORTHGATE DR Unit #100, PARKER, CO 80134
Building Code:
2012 IBC
Inspections
Contractors
Permit Fees
Property Details
Structure Details
Documents
JavaScript and Session Cookies must be enabled for this Site.
Scheduled Inspections
Name
Date Scheduled
Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters
Received Date
Inspection History
Name
Date Occurred
Result
Inspector Name
Inspection Comments
Meter Release
Inspection Report
Control Lighting
09/03/2019
Approved
Jim Dorsey
Print Report
Drywall
08/06/2019
Approved
Rick Chadwick
Print Report
Electric Trench
07/31/2019
Disapproved
Henry VanSchaack
) cannot use pvc for power to chairs per 517.13, redundant egc throughout; 2) corrosion protect 4s boxes on contact with concrete; 3) request slab inspection #73
Print Report
Final Building
08/30/2019
Approved
Rick Chadwick
Print Report
Final Electric
08/30/2019
Disapproved
Henry VanSchaack
1) receps in floor boxes require gfci; 2) em light in exam rm must be on local lighting ckt
Print Report
Final Electric
09/03/2019
Approved
Jim Dorsey
Print Report
Final Plumbing
08/29/2019
Disapproved
Rick Chadwick
PREP AREA SINKS NOT DRAINING PROPERLY BUBBLES AT BOTH SINKS
CAULK LAV MEN'S PERSONAL BATH RM
Print Report
Final Plumbing
08/30/2019
Approved
Rick Chadwick
Print Report
Rough Electric
07/31/2019
Disapproved
Henry VanSchaack
1) need p-rings and eg pigtails installed; 2) broken mc in wall at panoramic tray machine
Print Report
Rough Electric
08/07/2019
Approved
Jim Dorsey
walls ok
Print Report
Rough Electric Partial
07/24/2019
Disapproved
Jim Dorsey
not ready courtesy call
Print Report
Rough Plumbing
07/19/2019
Approved
Rick Chadwick
H2O LINE IN CEILING PLENT EXISTING CONDITION NO PIPE INS
Print Report
Slab Electrical
08/05/2019
Approved
Jim Dorsey
Emt coated slab on grade
Print Report