Building Permit Details
Permit Number: 17-13326
Permit Status: Completed
Permit Type: Building
Project Type: Residential
Description of Work: RS - Basement
Scope of Work: Alteration
Issued Date: 12/19/2017
CO Issue Date:
Plans Examiner: Stuart Foster
Job Address: 10036 COPENHAGEN ST PARKER, CO 80134
Building Code: 2012 IRC
Scheduled Inspections
Name Date Scheduled Estimated Time of Inspection
Engineering Letters
Engineering Letters will be listed below if they are required for your project. They must be submitted before scheduling above ground inspections.
Required Engineering Letters Received Date
Inspection History
Name Date Occurred Result Inspector Name Inspection Comments Meter Release Inspection Report
Drywall 02/28/2018 Disapproved Richard Miller cut float at all walls  
Drywall 03/05/2018 Approved Richard Miller  
Electric Service Equipment 03/19/2018 Disapproved Justin Lett Consult only-not ready  
Final Building 05/08/2018 Disapproved Richard Miller see ticket  
Final Building 05/31/2018 Approved Clayton Rodeback  
Final Electric 05/08/2018 Disapproved Henry VanSchaack rang doorbell twice, knocked, no one home 9:45 am  
Final Electric 05/31/2018 Disapproved Justin Lett See scanned ticket  
Final Electric 06/04/2018 Disapproved Justin Lett Disp and DW not permitted on SABC  
Final Electric 06/05/2018 Approved Justin Lett See scanned notes regarding final elec  
Final HVAC 05/08/2018 Approved Richard Miller  
Final Plumbing 05/08/2018 Approved Richard Miller  
Interior Gas Line 02/21/2018 Approved Richard Miller  
Rough Electric 02/21/2018 Disapproved Rich Edgett 1) EGCs in 3-gang at bottom of stairs not spliced together
2) 2nd bath fan incomplete
3) 30"W wotkspace required in front of subpanel
4) Bushing required on SER connector in subpanel
5) Recess cans in E bdrm closet must be 6" horiz from side wall shelf space
6) NM not permitted in conduit in slab on grade
7) 2 14-2 cables not permitted in pan box over island
8) Permanent access required to UFER
9) Max OCPD for #2 Al SERis 90A (Not a main feeder)
 
Rough Electric 02/22/2018 Approved Justin Lett  
Rough Frame 02/21/2018 Disapproved Richard Miller need minimum 2" float,need exhaust fan in south shower stall  
Rough Frame 02/22/2018 Approved Rick Chadwick  
Rough HVAC 02/21/2018 Approved Richard Miller  
Rough Plumbing 02/21/2018 Approved Richard Miller  
Shower Pan 02/22/2018 Disapproved Rick Chadwick NOT READY  
Shower Pan 03/01/2018 Disapproved Richard Miller need water test  
Shower Pan 03/02/2018 Approved Richard Miller  
Slab Electrical 03/20/2018 Approved Justin Lett Floor heat cable bsmt bath  
Underground Plumbing 12/20/2017 Approved Rick Chadwick